10 kV线路低频减载误动问题分析及改进  被引量:1

Misoperation Problem Analysis and Improvement of 10 kV Line Low Frequency Load Shedding

在线阅读下载全文

作  者:王彩丽 王俊辉 白海松 李海瑶 胡明会 WANG Cai-li;WANG Jun-hui;BAI Hai-song;LI Hai-yao;HU Ming-hui(Xuji Electric Co., Ltd, Xuchang 461 000, China)

机构地区:[1]许继电气股份有限公司,河南许昌461000

出  处:《电工电气》2017年第10期48-50,共3页Electrotechnics Electric

摘  要:针对某站10 k V线路低频减载发生误动作情况,通过对动作报告、录波、测频、保护逻辑进行分析,认为误动作是由于PT饱和产生分频分量及保护逻辑设计不合理造成的。提出针对性的逻辑优化方案,通过现场问题验证,解决了误动问题,并列举常见低频减载误动作情况及防误措施,避免再次发生低频减载误动作。In allusion to the misoperation situation happening in certain station of10kV line low frequency load shedding,this paperanalyzed the action report,the wave recording,the frequency measurement and the protection logic to find that the malfunction was causedby the fractional frequency component produced by PT saturation and the unreasonable design of protection logic.This paper proposed thespecific logic-optimized scheme,solved the problem of the misoperation by the site problem verification and enumerated the common lowfrequency load shedding misoperation situation and anti-misoperation measures to avoid the low frequency load shedding misoperation occurringagain.

关 键 词:低频减载 PT饱和 分频谐振 误动作 防误措施 

分 类 号:TM75[电气工程—电力系统及自动化]

 