玻璃纤维和熔喷化纤过滤器消静电前后的性能比较与分析  被引量:5

Comparison and Analysis of the Performance of Glass-fiber and Melt-blown Chemical Fiber Filter before and after Eliminating Static Electricity

在线阅读下载全文

作  者:侯银燕[1] 王志勇[1] 杨英霞[1] 李剑东[1] 徐昭炜[1] 王智超[1] Hou Yinyan;Wang Zhiyong;Yang Yingxia;Li Jiandong;Xu Zhaowei;Wang Zhichao

机构地区:[1]中国建筑科学研究院

出  处:《洁净与空调技术》2017年第2期28-30,共3页Contamination Control & Air-Conditioning Technology

摘  要:选取玻璃纤维过滤器和熔喷化纤过滤器,基于EN 779:2012标准,对其消静电前后的阻力、过滤效率和过滤器分级进行了实验研究。实验结果表明:1)消静电对两种材料的过滤器初阻力基本无影响;2)两种材料的过滤器在过滤效率基本相当的情况下,熔喷化纤过滤器阻力远低于传统的玻璃纤维过滤器;3)消除静电对熔喷化纤过滤器的过滤效率影响较大;4)静电是影响过滤器分级的一个重要因素。According to the EN779:2012standard,the resistance,filter efficiency and filter grade about glass-fiber filter and melt-blown chemical fiber filter were studied.The experimental results are shown below.1)The static electricity has no effect on the initial resistance of the two materials.2)Under the condition that the filtration efficiency of the two kinds of materials is basically the same,the resistance of the melt-blown chemical fiber filter is much lower than that of the traditional glass-fiber filter.3)The elimination of static electricity has great influence on the filtration efficiency of meltblown fiber filter.4)Static electricity is one of the most important factors affecting the classification of filters.

关 键 词:空气过滤器 静电 阻力 过滤效率 分级 

分 类 号:TU834.83[建筑科学—供热、供燃气、通风及空调工程]

 