作 者:李斌[1] 廖惠琴 戴冬康 姜宪国[2] 杜丁香[2] 李仲青[2] LI Bin;LIAO Huiqin;DAI Dongkang;JIANG Xianguo;DU Dingxiang;LI Zhongqing(Key Laboratory of Smart Grid of Ministry of Education(Tianjin University),Tianjin 300072,China;China Electric Power Research Institute,Beijing 100192,China)
机构地区:[1]天津大学智能电网教育部重点实验室,天津300072 [2]中国电力科学研究院,北京100192
出 处:《电力系统及其自动化学报》2017年第12期1-7,13,共8页Proceedings of the CSU-EPSA
基 金:国家自然科学基金资助项目(51277130)
摘 要:局部同塔输电线路两回线之间存在零序互感,当输电线路发生接地故障时,可能导致接地距离保护的误动或拒动。本文阐述了同塔双回输电线路的几种典型杆塔结构,计算了同塔双回输电线路线间零序互感大小,基于线间零序互感较严重的杆塔结构搭建了局部同塔双回输电线路的仿真模型,重点研究了局部同塔输电线路不同故障位置对接地距离保护的影响,并提出了相应的改进措施。通过PSCAD仿真软件验证了该方法的正确性与准确性。本文研究对局部同塔双回线路接地距离保护的改进,具有很重要的现实意义和实用价值。There is zero-sequence mutual inductance between two lines partially on the same tower,which may lead to mal-operation or refusal of ground distance protection when a ground fault occurs on the transmission lines.In this paper,several typical tower structures are introduced,and the zero-sequence mutual inductances between two double-circuit lines on the same tower are analyzed.A simulation model of double-circuit transmission lines partially on the same tower is founded based on the tower structure that has a larger zero-sequence mutual inductance.Specifically,the effects of different fault positions on the ground distance protection for the transmission lines partially on the same tower are analyzed,and the corresponding improvement measures are proposed.The correctness and accuracy of the proposed method are verified by PSCAD.The research in this paper has practical significance and values for the improvement of ground distance protection of the double-circuit transmission lines partially on the same tower.
关 键 词:局部同塔 零序互感 测量阻抗 故障位置 接地距离保护
分 类 号:TM761[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.249