作 者:雷霖 唐成达 青禹成 张鹏 赖真良 赵永鑫 LEI Lin;TANG Chengda;QING Yucheng;ZHANG Peng;LAI Zhenliang;ZHAO Yongxin(School of Electronic and Electrical Engineering,Xihua University,Chengdu 610039,China;School of Information Science and Electrical Engineering,Chengdu University,Chengdu 610106,China)
机构地区:[1]西华大学电气与电子信息学院,四川成都610039 [2]成都大学信息科学与工程学院,四川成都610106
出 处:《电力系统保护与控制》2018年第18期149-155,共7页Power System Protection and Control
基 金:四川省科技厅重点研发项目(2017GZ0385)~~
摘 要:为解决逆变器控制策略对含逆变型分布式电源的配电网的故障特性的影响问题,提出了一种基于正序分量综合阻抗的纵联保护新原理。该原理利用线路两端正序电压相量之差与线路两端正序电流相量之和的比值构成正序分量综合阻抗。区内与区外发生故障时,正序分量综合阻抗的幅值变化明显,据此可以区分线路上的内部和外部故障。新原理特征量明显,容易整定,不受分布式电源控制策略的影响,抗过渡电阻能力强。PSCAD仿真验证了该原理的有效性。In order to solve the influence of the inverter control strategy on the fault characteristics of the distribution network with Inverter Interfaced Distributed Generator(IIDG),a new principle of pilot protection based on positive sequence component integrated impedance is proposed.The principle uses the ratio between the difference of two terminals positive sequence voltage phasor of the transmission line and the sum of the two terminals positive sequence currents phasor of the same transmission line to form a positive sequence component integrated impedance.When the faults occur in external or internal area,the amplitude of the positive sequence component integrated impedance varies obviously,so that the internal and external faults on the line can be distinguished.The new principle has obvious characteristics,such as easy tuning,free from the influence of distributed generation control strategy,and strong resistance to transition resistance.The validity of the principle is verified by PSCAD simulation.
关 键 词:正序分量综合阻抗 纵联保护 正序分量 逆变型分布式电源 配电网
分 类 号:TN86[电子电信—信息与通信工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49