高压高频振荡波检测电抗器匝间故障技术探讨  

Discussion on Turn-to-turn Fault of High Voltage and High Frequency Oscillation Detection Reactor

在线阅读下载全文

作  者:白广三 王韧 张云 孙再超 宋斌 罗恒 BAI Guangsan;WANG Ren;ZHANG Yun;SUN Zaichao;SONG Bin;LUO Heng(Lincang Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Lincang 677000,China)

机构地区:[1]云南电网有限责任公司临沧供电局,云南临沧677000

出  处:《电工技术》2018年第21期140-141,共2页Electric Engineering

摘  要:针对传统方法难以检测出干式空心电抗器的匝间绝缘缺陷的问题,在国标基础上设计了高压高频振荡波检测装置。在现场采用该装置测试了10kV并联电抗器,发现B相电抗器两个高频波的衰减速度和频率不一致,确定B相电抗器存在匝间绝缘故障,验证了其可靠性。As is difficult to detect the inter turn-to-turn insulation defects of dry-type air-core reactor,the high voltage and high frequency oscillation detection device was designed on the basis of national standard.When the device was used to test the 10kV shunt reactor,it was found that the attenuation speed of the two high frequency waves of the B phase reactor were inconformity,which identified that B phase reactor had an turn-to-turn insulation fault.The test results verified the reliability of the detection device.

关 键 词:高压高频振荡波 干式空心电抗器 匝间绝缘 

分 类 号:TM47[电气工程—电器]

 