某220kV变压器短路损坏的原因分析  

Analysis of Short Circuit Damage of a 220kV Transformer

在线阅读下载全文

作  者:滑勉 卢洪宝 李新星[1] HUA Mian;LU Hongbao;LI Xinxing(State Shanxi Electric Power Corporation,Taiyuan,Shanxi 030001,China)

机构地区:[1]国网山西省电力公司,山西太原030001

出  处:《山西电力》2019年第1期14-18,共5页Shanxi Electric Power

摘  要:介绍了一起近区短路引起220kV变压器损坏的事故。事故中,C相低压绕组在3个导线换位处(S弯)发生了短路、断股,分析认为绕组工艺问题、楔形垫块松动、未考虑S弯处自粘换位导线在高温下的粘合强度是主要原因,并对事故后变比试验的错误数据进行了说明。通过查阅文献,发现曾发生若干起类似事故,建议该共性问题引起重视。An accident involving a 220 kV transformer damage caused by short circuit in the near area was analyzed.After accidents,it is found that three cases of short-circuit and strand breakage occurred at where wires transposed at C-phase low-voltage windings.Analysis led to the conclusion that the winding process problem,loose wedge-shaped block,and less consideration on the adhesive strength of self-adhesive transposed wires under high-temperature are the main reasons for the accident.Erroneous data of the post-accident ratio test was expounded.By consulting the literature,it is found that several similar accidents have ever happened and it is suggested that the common problems should be aroused attention.

关 键 词:变压器 换位导线 粘合强度 变比试验 

分 类 号:TM41[电气工程—电器]

 