摘 要:简单介绍了医院影像科与核医学科设备机房空调要求。结合南京市某医院工程实例,分析了溶液调湿新排风空调与恒温恒湿空调这两种方案的系统构成、空气处理过程、适用特性、初投资。利用华电源能耗模拟软件,对全年空调负荷、全年空调系统耗电量进行模拟计算,结果显示这两种方案都可以满足机房的温湿度要求,恒温恒湿空调方案初投资低14.4%,溶液调湿新排风空调方案年耗电量低17.3%。This paper briefly introduces the airconditioning requirements of hospital imaging department and nuclear medicine equipment room. Taking a case study of a hospital project in Nanjing, the liquid desiccant fresh air and exhaust air conditioning with constant temperature and humidity air conditioning was analyzed, including the system structure, air handling process, and initial investment. Using HDY energy consumption simulation software, the yearround air conditioning load and the power consumption of air conditioning systems all the year round was simulation calculated. Results show that the two schemes can satisfy the requirement of the room temperature and humidity, and constant temperature and humidity air conditioning scheme is 14.4% lower initial investment, and the solution of new wet exhaust air conditioning scheme year was 17.3% lower power consumption.
关 键 词:医院影像科与核医学科设备机房 溶液调湿新排风空调 恒温恒湿空调
分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]