吹吸式通风送排风罩面积倒挂时排风罩面积对极限流量比的影响  

Influence of exhaust hood area on limit flow ratio for push-pull ventilation under condition of exhaust hood area smaller than supply hood area

在线阅读下载全文

作  者:周书林[1] 杨斌[1] 梁莎莎 张笑飞 Zhou Shulin;Yang Bin;Liang Shasha;Zhang Xiaofei(China Academy of Safety Science and Technology,Beijing, China)

机构地区:[1]中国安全生产科学研究院,100029 [2]北京科技大学

出  处:《暖通空调》2019年第6期22-24,共3页Heating Ventilating & Air Conditioning

基  金:“十三五”国家重点研发计划项目(编号:2016YFC0801700)

摘  要:在吹吸式通风实验室搭建了实验平台,排风罩面积小于送风罩。在保证其他条件不变的情况下,改变排风罩面积,通过示踪气体法确定将给定送风完全排走的最小排风量,反推极限流量比。实验结果显示,在上述实验条件下,排风罩面积的改变会对极限流量比产生影响,且送排风罩面积倒挂差距越大,极限流量比越大。Develops an experimental platform in the push-pull ventilation laboratory, whose exhaust hood area is smaller than supply hood area. Under the condition of the same parameters, determines the minimum exhaust air rate that completely discharges the given supply air rate by the tracer gas method, and deduces the limit flow ratio. The experimental results show that under the above experimental conditions, the change of exhaust hood area will affect the limit flow ratio, and the larger the gap between the areas of the exhaust hood and the air supply hood, the higher the limit flow ratio.

关 键 词:吹吸式通风 排风罩面积 排风量 流量比法 送风量 

分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]

 