检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:ZHONG Xiaohui YANG Hailong YANG Ke XU Jianzhong
机构地区:[1]Institute of Engineering Thermophysics,Chinese Academy of Sciences,Beijing 100190,China [2]College of Metallurgy and Energy,North China University of Science and Technology,Tangshan 063009,China
出 处:《Journal of Thermal Science》2019年第4期635-642,共8页热科学学报(英文版)
基 金:supported by the Natural Science Foundation of Beijing Municipality(3172040);National Natural Science Foundation(51736008);Strategic Priority Research Program of the Chinese Academy of Sciences(XDA21050600)
摘 要:A new-type multiple-source heat pump cycle with two-stage compression was established on the basis of the problems of similarly existing heat pumps.The equivalent temperature levels of typical evaporators are applied to the different heat sources of the proposed cycle,and the high-temperature heat sources are shown to enhance vapor injection.Then,the mathematical model and prototype are developed,and the results from experimental simulation and validation showed that the solar collector can improve the heating performance of the proposed heat pump system.In the middle-temperature heating period,the outdoor temperature is less than-25℃,and the average coefficient of performance(COP)value of the proposed heat pump was 4.2,which was greater than the COPs of conventional ground source heat pumps.A new-type multiple-source heat pump cycle with two-stage compression was established on the basis of the problems of similarly existing heat pumps. The equivalent temperature levels of typical evaporators are applied to the different heat sources of the proposed cycle, and the high-temperature heat sources are shown to enhance vapor injection. Then, the mathematical model and prototype are developed, and the results from experimental simulation and validation showed that the solar collector can improve the heating performance of the proposed heat pump system. In the middle-temperature heating period, the outdoor temperature is less than-25°C, and the average coefficient of performance(COP) value of the proposed heat pump was 4.2, which was greater than the COPs of conventional ground source heat pumps.
关 键 词:multiple-source heat PUMP TWO-STAGE compression SOLAR COLLECTOR simulation