风电接入配电网的自适应电流速断保护研究  

Study on Adaptive Current Quick-break Protection for Wind Power Access Distribution Power Network

在线阅读下载全文

作  者:王宝锋 WANG Baofeng(Xi′an Xirui Control Technology Co. , Ltd. , Xi′an 710077, China)

机构地区:[1]西安西瑞控制技术股份有限公司

出  处:《电工技术》2019年第17期53-54,57,共3页Electric Engineering

摘  要:分析了风电接入配电网对电流保护的影响,提出了自适应电流速断保护方案,并对其实现过程中的关键点进行了论述。RTDS试验结果表明,对于风电接入的配电网,自适应电流速断保护能适应系统运行方式和故障类型的变化,保护范围稳定,具有很好的适用性。The influence of wind power access distribution powernetwork on current protection was analyzed.Ascheme of an adaptive current quick-break protectionwasproposed. Then, the three key points duringrealization the theorywas discuss. Finally, the result of RTDS test showed that the adaptive current quick-break protection couldnot only fit to the running mode of the system and the various fault typesbut alsohad a stableprotective range of line length, and it was good application in thedistribution power network.

关 键 词:自适应电流速断保护 相电流突变量 RTDS试验 

分 类 号:TM771[电气工程—电力系统及自动化]

 