作 者:尹湘源[1,2] 尹项根 曹文斌[1,2] 王育学[3] 潘远林 陈永昕 YIN Xiangyuan;YIN Xianggen;CAO Wenbin;WANG Yuxue;PAN Yuanlin;CHEN Yongxin(State Key Laboratory of Advanced Electromagnetic Engineering and Technology,Huazhong University of Science and Technology,Wuhan 430074,China;Hubei Electric Power Security and High Efficiency Key Laboratory,Huazhong University of Science and Technology,Wuhan 430074,China;Electric Power Dispatching Control Center of Guangdong Power Grid Co.,Ltd.,Guangzhou 510600,China)
机构地区:[1]强电磁工程与新技术国家重点实验室(华中科技大学),湖北武汉430074 [2]电力安全与高效湖北省重点实验室(华中科技大学),湖北武汉430074 [3]广东电网有限责任公司电力调度控制中心,广东广州510600
出 处:《电力系统保护与控制》2019年第20期91-96,共6页Power System Protection and Control
基 金:国家重点研发计划项目资助(2016YFB0900600);广东电网有限责任公司科技项目资助(GDKJXM20162461)~~
摘 要:从分析变压器暂态涌流特性出发,致力于得到变压器各侧漏感值。首先推导了变压器回路方程,然后得到了原方零模电流和三角绕组环流的比例关系,并求出了自漏感表达式。针对220 kV变压器三角绕组环流无法测量的问题,基于三角绕组环流与原方不饱和相电流平衡的特点,采用原方不饱和相电流代替环流。从而求出零模电流与选定的不饱和相电流的准比例系数,进一步通过判别不饱和时间区间,以该区间内的平均值作为所求的比例系数,最后通过上述表达式计算出自漏感。该方法通过了改进变压器模型仿真验证和现场录波的应用。In order to analyze the transient inrush current characteristics of the transformer, it is necessary to obtain the accurate leakage inductance value on each side of the transformer. In this paper, the transformer loop equation is first deduced, the proportional relationship between the primary zero-mode current and the delta circulating current is got, and the self-leakage expression is obtained. For the problem that the delta winding current of 220 kV transformer cannot be measured, the primary unsaturated phase current is used instead of the circulating current based on the balance of the delta winding circulating current and the primary unsaturated phase current. After determining the quasi-proportional coefficient of the selected unsaturated phase current and the zero-mode current, the unsaturated time interval is further determined, and the average value in the interval is used as the obtained proportional coefficient. Finally, the self-leakage is calculated by the above expression. The improved transformer model simulation and on-site recording verify the method.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.117