作 者:彭忠 魏金科 赵静 李泰 荆雪记 苏进国 胡永昌 李艳梅 袁飞 PENG Zhong;WEI Jinke;ZHAO Jing;LI Tai;JING Xueji;SU Jinguo;HU Yongchang;LI Yanmei;YUAN Fei(XJ Electric Co.,Ltd.,Xuchang 461000,China;Light Industry Vocational University of Henan Province,Zhengzhou 450002,China;China Electric Power Technology and Equipment Co.,Ltd.,Beijing 100058,China)
机构地区:[1]许继电气股份有限公司,河南许昌461000 [2]河南省轻工业职工大学,河南郑州450002 [3]中国电力技术装备有限公司,北京100058
出 处:《电力系统保护与控制》2019年第16期180-187,共8页Power System Protection and Control
基 金:国家重点研发计划项目资助(2016YFB0900603);国家电网公司科技项目资助(52094017000W)~~
摘 要:LCC通过反转电压极性实现整流和逆变的转换,可能导致并联型多端直流输电系统功率短时中断。为此,提出一种基于LCC的并联型三端直流输电系统接线方案,分析可能存在的运行方式及转换方法,提出极性转换、电压控制站投退的控制顺序和故障极紧急停运策略。基于PSCAD/EMTDC平台建立三端直流输电系统仿真模型,仿真极性转换、电压控制站投退和故障极紧急退出实验。仿真结果表明该多端系统换流站功率反转不影响其余换流站功率稳定运行,并且能够安全隔离故障设备,快速恢复健全系统稳定运行。LCC conversion between rectification and inversion by voltage reversal may force multi-terminal HVDC transmission system to be power interrupted for a short time.So a connection scheme based LCC for parallel three terminal HVDC transmission system is presented,the possible operation modes and conversion methods are analyzed,the control sequences of pole conversion and DC voltage controlling station input and output and emergency exit strategy for fault pole are presented.Based on the platform of PSCAD/EMTDC,the three terminal HVDC simulation model is built to carry out the simulation on pole conversion,DC voltage controlling station input and output,and emergency exit of fault pole.The simulation results show that power reversal of one converter station based the multi-terminal HVDC would not affect others station,and could isolate fault devices safely to recover the stable operation of sound system quickly.
关 键 词:并联型多端直流输电 接线方案 运行方式 控制策略 紧急停运
分 类 号:TM7[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7