作 者:张廼龙 贾勇勇 李鸿泽 路永玲 刘子全 方春华[3] 张威 李景 ZHANG Nai-long;JIA Yong-yong;LI Hong-ze;LU Yong-ling;LIU Zi-quan;FANG Chun-hua;ZHANG Wei;LI Jing(Research Institute, State Grid Jiangsu Electric Power Co., LTD., Nanjing 211103, China;State Grid Jiangsu Electric Power Co., LTD, Nanjing 210024, China;College of Electrical Engineering and New Energy, CTGU, Yichang 443002, China)
机构地区:[1]国网江苏省电力公司电力科学研究院,南京211103 [2]国网江苏省电力有限公司,南京210024 [3]三峡大学电气与新能源学院,宜昌443002
出 处:《科学技术与工程》2019年第35期193-200,共8页Science Technology and Engineering
摘 要:为研究±800 kV输电线路所使用的横担较长的铁塔在受到台风载荷作用时的时程响应分析,通过建立三塔两线有限元模型,基于风速不随高度变化的Von Karman谱,利用谐波叠加法生成了基准风速为50 m/s的风速时程,应用模拟的台风载荷进行时长为50 s的时程分析,共分析了风载荷45°、60°、90°作用下塔线体系的三种情况。仿真结果显示,在45°和60°风作用下,铁塔中部、塔头和塔身连接的平口处应力超过屈服强度,导、地线挂线板处所受应力也超限,铁塔在90°风作用时,塔身腰部主材和塔腿主材应力也超过屈服强度。要预防台风对铁塔的破坏,应该从上述三个部位对铁塔进行补强,在塔腿及塔腰之间增加水平材是一种有效的加固措施。In order to study the time history response of a tower with a long cross-bearing used in ±800 kV transmission lines under typhoon loads, a three-tower two-line finite element model is established. Based on the Von Karman spectrum of wind speed which does not vary with height, the wind speed time history with a reference wind speed of 50 m/s is generated by the harmonic superposition method as a simulated typhoon load. The time history analysis of the tower-line system with wind load of 45°, 60° and 90° is carried out. The simulation results show that under the action of 45° and 60° wind, the stress at the flat junction of the central part of the tower, the head of the tower and the tower body exceeds the yield strength, and the stress at the conductor and the ground wire hanging plate also exceeds the limit. When the tower is under the action of 90° wind, the stress of the main material at the waist of the tower body and the main material at the leg of the tower also exceeds the yield strength. To prevent the damage of typhoon to the tower, the tower should be reinforced from the above three parts. It is an effective reinforcement measure to add horizontal material between tower leg and tower waist.
关 键 词:台风 三塔两线 补强 Von Karman谱 谐波叠加法
分 类 号:TM751[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.117