除霜溶液冷冻再生的可行性分析  被引量:1

Applicability analysis on freezing-regeneration of defrosting-solution

在线阅读下载全文

作  者:杨剑[1] 余延顺[1] Yang Jian;Yu Yanshun(Nanjing University of Science and Technology)

机构地区:[1]南京理工大学

出  处:《制冷与空调》2019年第12期87-92,共6页Refrigeration and Air-Conditioning

摘  要:针对空气源热泵除霜溶液的冷冻再生问题,利用R407C非共沸混合制冷剂的变温蒸发特性满足除霜溶液的再生温度要求,从而实现溶液的冷冻再生。本文对制热工况下制冷剂的非共沸特性进行相关试验研究,并采用Solidworks软件进行机组模型的构建,针对R407C滑移温度的特性,对机组的再生温度、除霜溶液浓度以及机组蒸发温度三者之间进行匹配计算和分析。结果表明,采用R407C制冷剂的机组比采用R22制冷剂的机组蒸发侧压损减少38%,证明R407C制冷剂用于空气源热泵除霜溶液冷冻再生的可行性。Aimed at the issue of freezing-regeneration of defrosting-solution in air source heat pump,the variable-temperature evaporating characteristics of R407C non-azeotropic mixed refrigerant are used to meet the regeneration temperature requirement of the defrosting-solution,so as to realize the freezing-regeneration of the solution.Therefore,the experimental study on the non-azeotropic characteristics of refrigerant under heating conditions,and the unit model is established using Solidworks software.According to the characteristics of R407C slip temperature difference,the matching calculation and analysis on the unit s regeneration temperature,concentration of defrosting-solution and evaporating temperature of unit are performed.The results show that the pressure loss of unit with R407C at the evaporating side is reduced by 38%compared with that of the unit with R22,which proves the feasibility of R407C applied to the freezing-regeneration of defrosting-solution in air source heat pump.

关 键 词:空气源热泵 冷冻再生 除霜溶液 R407C 滑移温度 再生温度 

分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象