作 者:肖海波 晏飞 王志 刘磊 XIAO Hai-bos YAN Fei;WANG Zhi;LIU Lei(State Grid Xinyuan Company LTD.Huilong Branch,Nanyang 473000,China)
机构地区:[1]国网新源控股有限公司回龙分公司,河南南阳473000
出 处:《水电站机电技术》2019年第S01期7-8,24,76,共4页Mechanical & Electrical Technique of Hydropower Station
摘 要:抽水蓄能机组由于水头高、机组转速高和水流双向运行的特性,必须配置机组振摆保护装置。回龙蓄能电站机组配置了独立振摆监测装置及振摆保护装置。针对不同工况下振摆数值相差较大的特点,按负荷区分稳定工况区和不稳定工况区,分别设置报警定值、延迟时间、停机逻辑,确保了机组全过程的安全运行。停机逻辑判断及延时时间由振摆保护装置完成,其停机输出直接作用于紧急停机回路,不再通过监控判断,保证了振摆保护装置开出的及时性和真实性。优化通道配置方式,实现了同一部位冗余测点分布在不同监测采集模块,从而避免了某一监测模块出现故障导致误停机。Since a pumped storage unit features high head,high speed and operation under bidirectional flow,it must be equipped with a vibration and runout protection device.The unit of the Huilong Pumped Storage Power Station is equipped with independent vibration and runout monitoring device and corresponding protection device.Considering large numerical difference in vibration and runout under different operating conditions,stable and unstable operating condition areas are distinguished from each other based on load.Meanwhile,these devices are also equipped with alarm setting,delay time and shutdown logic to ensure safe operation of the unit in the whole process.The shutdown logic judgment and the delay time are completed by the vibration and runout protection device,and the shutdown output of the device directly acts on the emergency shutdown circuit without monitoring judgment,thus ensuring the timeliness and authenticity of the vibration and runout protection device.The channel configuration mode is optimized,so that redundant measuring points at the same part are distributed in different monitoring and acquisition modules,thus avoiding unwanted shutdown due to failure of one monitoring module.
分 类 号:TM774[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.171