某抽水蓄能电站SFC输入变压器C2H2含量超标原因分析与处理  

Cause Analysis and Treatment of Excessive C2H2 Content of SFC Input Transformer in a Pumped-storage Power Station

在线阅读下载全文

作  者:杨剑 黄艳[2] 仲鸣 高从闯 YANG Jian;HUANG Yan;ZHONG Ming;GAO Congchuang(Jiangsu Guoxin Liyang Pumped-storage Power Generating Co.,Ltd.,Liyang 213334,China;Jiangsu Shahe Pumped-storage Power Generating Co.,Ltd.,Liyang 213333,China)

机构地区:[1]江苏国信溧阳抽水蓄能发电有限公司,江苏溧阳213334 [2]江苏沙河抽水蓄能发电有限公司,江苏溧阳213333

出  处:《电工技术》2020年第1期137-139,共3页Electric Engineering

摘  要:某抽水蓄能电站运行1年多,#1SFC输入变压器出现C2H2含量超标问题。通过对油样检测数据的跟踪分析,判定变压器内部存在电弧放电现象。先采取真空循环滤油方法保证变压器安全稳定运行,再采取变压器吊芯检修措施有效解决变压器C2H2含量超标问题。A pumped storage power station had been in operation for more than 1 year and the problem of excessive acetylene content of No.1 SFC input transformer was occurred.Through tracking and analyzing of the testing data of oil samples,the presence of arcing inside the transformer was determined.Firstly,the method of vacuum circulation oil filtering was adopted to ensure the safe running of the transformer.Then,the maintenance of the transformer by hoisting core was adopted and the problem of excessive C2H2 content of transformer was effectively controlled.

关 键 词:SFC 输入变压器 C2H2 放电 抽水蓄能电站 

分 类 号:TM407[电气工程—电器]

 