某220kV变电站跳位监视回路设计缺陷分析及改进  

Analysis and Improvement of the Design Defects of the Close Position Monitoring Circuit in a 220 kV Substation

在线阅读下载全文

作  者:金豫杰 黄鹤锋 黄潇潇 JIN Yujie;HUANG Hefeng;HUANG Xiaoxiao(Baise Electric Power Co.,Ltd.,Guangxi Baise 533000,China)

机构地区:[1]百色电力有限责任公司,广西百色533000

出  处:《广西电力》2020年第1期47-52,共6页Guangxi Electric Power

摘  要:针对某220 kV变电站跳位监视回路的设计缺陷问题,通过对保护装置和断路器合闸控制回路的设计及接线原理进行分析,发现跳位监视回路存在监视盲区,导致控制回路断线时保护装置和后台未能正确提示并告警。对跳位监视回路的二次接线改进后,成功消除了跳位监视回路监视盲区的问题,提高了系统供电可靠性和安全稳定性。Aimed at solving the design defect problem of the close position monitoring circuit in a 220 kV substation,the design of the protection equipment and the closing control circuit of the circuit breaker and the connection principles are analyzed.It is found that the protection equipment and background didn't send the pop-up message and warning correctly when the control circuit was disconnected,due to the existence of blind areas in the close position monitoring circuit.After the modification of the secondary connection in the close position monitoring circuit,the problem of blind areas in the close position monitoring circuit is successfully eliminated,thus improves the power supply reliability and security&stability of the system.

关 键 词:跳位监视回路 断路器 保护装置 设计缺陷 

分 类 号:TM561[电气工程—电器] TM63

 