核电厂消防水泵最小流量旁通管孔板空泡腐蚀研究与对策  

Cavitation Corrosion Research and Countermeasure of Minimum Flow Bypass Tube Orifice Plate of Fire Pump in Nuclear Power Plant

在线阅读下载全文

作  者:苏斌 王水勇[2] Bin Su;Shuiyong Wang(Operation Standardization Center of Zhongguang Nuclear Operations Co.,Ltd.,Shenzhen,Guangdong,518000,China;Life Management Technology Center of Suzhou Thermal Research Institute Co.,Ltd.,Suzhou,Jiangsu,210000,China)

机构地区:[1]中广核运营有限公司运营标准化中心,广东深圳518000 [2]苏州热工研究院有限公司寿命管理技术中心,江苏苏州210000

出  处:《工程技术研究(百科)》2019年第1期52-56,共5页Engineering technology research

摘  要:核电厂消防水生产系统每台消防水泵均在出口位置设置了1个节流孔板,用来控制流量的最小流量旁通管路,管壁腐蚀穿孔多次出现在这条最小流量旁通管道上。通过分析腐蚀形貌,开展流体力学计算,分析了管道腐蚀泄漏原因,改进了原设计方案。Each fire pump in the fire water production system of nuclear power plant has a throttle orifice plate at the exit to control the minimum flow bypass pipeline.Corrosion perforation on the wall of the pipeline occurs many times in the minimum flow bypass pipeline.Through the analysis of corrosion morphology and hydrodynamic calculation,the causes of pipeline corrosion leakage are analyzed,and the original design scheme is improved.

关 键 词:消防水泵 最小流量旁通管路 空泡腐蚀 流体力学 多级节流 

分 类 号:TM6[电气工程—电力系统及自动化]

 