作 者:何柏娜[1] 宁家兴 黄桂春[1] 孔杰 王乐淼 颉雅迪 姜仁卓 毛亚哲 周宇洋 HE Baina;NING Jiaxing;HUANG Guichun;KONG Jie;WANG Lemiao;XIE Yadi;JIANG Renzhuo;MAO Yazhe;ZHOU Yuyang(College of Electrical and Electronic Engineering,Shandong University of Technology,Zibo 255049,China)
机构地区:[1]山东理工大学电气与电子工程学院,山东淄博255049
出 处:《电力自动化设备》2020年第4期178-184,共7页Electric Power Automation Equipment
基 金:国家自然科学基金资助项目(51777130)。
摘 要:现有自适应重合闸在识别出瞬时性故障后普遍经过固有延时合闸,忽视了故障点电弧熄灭与否,为进一步提高重合闸的自适应能力,有必要对故障熄弧时刻进行识别。通过计算分析超高压线路接地点熄弧前后故障相端电压特性,对比发生瞬时性故障时故障相端电压绝对值函数在二次电弧阶段和恢复电压阶段的差异,发现二次电弧阶段绝对值函数的积分在相邻时间窗内大小始终不变,积分比约为1,而恢复电压阶段初期相邻时间窗内的积分存在显著差异,其积分比出现较为明显的突变。通过设定上下阈值,将故障相端电压绝对值函数积分比作为熄弧时刻识别判据,若积分比连续5次超过所设阈值,则判断故障熄弧。大量EMTP-ATP仿真表明,该判据能可靠识别熄弧时刻,且不受并联补偿度、故障位置以及过渡电阻影响,具有较强的自适应性。The existing adaptive reclosure usually recloses by inherent delay after transient fault is identi fied,and ignores whether the arc has extinguished at the fault point.So it is necessary to identify the time of the fault arc extinguishing to further improve adaptive capability of reclosure.The characteristics of fault phase terminal voltage of EHV(Extra High Voltage)transmission lines before and after arc extingui-shing are calculated and analyzed.The difference of absolute value function about fault phase terminal vol-tage at the stage of secondary arc and recovery voltage when transient fault occurs is compared.It is found that the integral of the absolute value function at the stage of secondary arc is always unchanged in adjacent time windows,and the integral ratio is about 1.However,the integral in adjacent time windows at the initial stage of recovery voltage is significantly different,and the integral ratio shows obvious mutation.The integral ratio of absolute value function about fault phase terminal voltage is used as a criterion for identification of extinguishing time by setting up and down threshold values.If the integral ratio exceeds the threshold value five times in a row,the arc distinguishing is judged.A large number of EMTP-ATP simulations show that the proposed criterion can identify the extinguishing time reliably,and is immune to parallel compensation degree,fault location and fault resistance,so it has strong adaptability.
关 键 词:超高压输电 瞬时性故障 故障相端电压 并联电抗器 积分比 熄弧时刻
分 类 号:TM77[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.3