UPS系统与市电不同步引发的DCS系统元件烧损原因分析  被引量:1

Cause Analysis of DCS Component Burn Caused by Power Asynchronous between UPS System and Mains

在线阅读下载全文

作  者:常新海[1] 高雪峰 曹强[1] CHANG Xinhai;GAO Xuefeng;CAO Qiang(The Energy Center of Jiuquan Iron and Steel Group,Jiayuguan,Gansu 735100,China)

机构地区:[1]酒钢(集团)能源中心,甘肃嘉峪关735100

出  处:《冶金动力》2020年第4期8-10,共3页Metallurgical Power

摘  要:通过对UPS旁路停电UPS输出失去同步基准引发的DCS多个供电原件过电压烧损事件分析,查找出DCS供电系统存在的寄生回路,制订消除寄生回路方法,提高DCS供电可靠性。Based on the analysis of the over-voltage burn-out event of several DCS power supply components caused by UPS output out of synchronization benchmark due to UPS bypass power failure,the parasitic circuit of DCS power supply system was found out,and the method of eliminating the parasitic circuit was formulated to improve the reliability of DCS power supply.

关 键 词:UPS系统 同步 寄生回路 

分 类 号:TM912[电气工程—电力电子与电力传动]

 