通信机房风冷专用空调长管路下的系统设计  被引量:1

System Design of Telecommunication Buildings Air Conditioner with Long Refrigerant Piping

在线阅读下载全文

作  者:赵路平 ZHAO Lu-ping(China Mobile Group Design Institute Co.,Ltd.Shanghai Branch)

机构地区:[1]中国移动通信集团设计院有限公司上海分公司

出  处:《建筑热能通风空调》2020年第2期96-99,共4页Building Energy & Environment

摘  要:风冷专用空调冷媒管管长对制冷衰减量有着重要影响,有些老旧通信机房受制于建筑本身制约,不得不采用长管路设计,然行业内尚没有长管路下的设计标准或指南,对系统设计带来一定困难。本文通过某通信机房的空调设计与分析,并借鉴多联机设计思路和方法,提出了风冷专用空调长管路下的设计方法,为类似项目提供设计参考。The length of the refrigerant piping of air-cooled direct expansion air conditioner has an important influence on the cooling capacity. Some telecommunication buildings have to use the long refrigerant piping due to some reasons,but currently there is no any design specifications to have relevant description, which brings difficulty for the designer. In this paper, through the system design of air conditioner for certain telecommunication building with the long refrigerant piping, the design method is proposed by referring to the design method of the VRV, which provides the design reference for similar projects.

关 键 词:通信机房 风冷专用空调 冷媒管超长 冷量衰减 润滑油回油 

分 类 号:TU831.3[建筑科学—供热、供燃气、通风及空调工程]

 