检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:辛成涛 乔刚 Xin Cheng-tao;Qiao Gang
机构地区:[1]烟台国网中电电气有限公司,山东烟台264000
出 处:《电力系统装备》2020年第13期191-192,共2页Electric Power System Equipment
摘 要:由于交交变频系统轧钢运行过程中频繁存在换相短路现象,此时系统电压突降,容易造成静止同步补偿器(Static Synchronous Compensator,简称STATCOM)装置过压过流.针对此问题,对STATCOM进行了改进,优化了控制算法,增大了进线电抗器阻值,增大了直流侧电容容量.改进后的STATCOM装置运行良好,现场功率因数得到明显提高,变压器温升得到明显降低.Due to the frequent commutation and short circuit in the process of rolling operation of AC-AC frequency conversion system,the sudden drop of system voltage is easy to cause over-voltage and over-current of static synchronous compensator(STATCOM)device.Aiming at this problem,STATCOM is improved.The control algorithm is optimized,the resistance of the incoming reactor is increased,and the capacitance capacity of the DC side is increased.The improved STATCOM device runs well,the fi eld power factor is signifi cantly improved,and the temperature rise of transformer is signifi cantly reduced.
分 类 号:TM615[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.170