检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:Yeuntae Yoo Seungmin Jung Gilsoo Jang
机构地区:[1]Korea University,Seoul,Korea [2]Hanbat National University,Daejeon,Korea
出 处:《Journal of Modern Power Systems and Clean Energy》2020年第2期260-266,共7页现代电力系统与清洁能源学报(英文)
基 金:supported by the framework of international cooperation programs managed by the National Research Foundation of Korea(No.2017K1A4A3013579);the Korea Institute of Energy Technology Evaluation and Planning(KETEP)grant funded by the Korea government(MOTIE)(No.20183010025440)。
摘 要:In recent years,the expansion of renewable energy in electric power systems has been increasing at such a rapid pace that it has started affecting frequency stability.Renewable generators connected to the grid produce variable amounts of power,and in most cases have no inherent inertia response(IR)to the system frequency.Therefore,the high penetration of renewable generators in the system results in low inertia and frequency distortion.If renewable generators account for a high proportion of the supply in a power system,the use of energy storage systems(ESSs)with frequency-support algorithms(in the place of synchronous generators)can stabilize the network.The participation of ESSs in frequency support must be organized precisely,so that they are fully devoted to their own purpose.In this paper,the frequency-support parameters of ESSs are calculated for achieving stable frequency response from a network.An estimation and calibration process is conducted during the active power-order change of the ESSs in the substation,and is verified through electromagnetic-transients-including-DC(EMTDC)-based simulations.
关 键 词:Energy storage system(ESS) frequency response INERTIA renewable energy substation
分 类 号:TM73[电气工程—电力系统及自动化] TK02[动力工程及工程热物理]