检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:周丹 马志钦 杨贤 温爱辉 靳宇晖 姜烁 ZHOU Dan;MA Zhi-qin;YANG Xian;WEN Ai-hui;JIN Yu-hui;JIANG Shuo(Guangdong Key Laboratory of Electric Power Equipment Reliability(Electric Power Research Institute of Guangdong Power Grid Co.,Ltd),Guangzhou 510080,China;Guangdong Power Grid Co.,Ltd,Guangzhou 510060,China)
机构地区:[1]广东省电力装备可靠性企业重点实验室(广东电网有限责任公司电力科学研究院),广东广州510080 [2]广东电网有限责任公司,广东广州510060
出 处:《电工电气》2020年第8期22-27,42,共7页Electrotechnics Electric
基 金:广东电网有限责任公司科技项目(GDKJXM20180150)。
摘 要:结合工程实际,分析了介质损耗角正切值tanδ在线监测的误差影响因素。建立了考虑多元件参量包括套管、电流传感器、信号通道以及信号调理单元的复杂等值电路模型,通过试验得到了电路模型中主要的等效电气参数。搭建了高、低压试验平台以模拟套管介损测量,模拟在复杂电磁及大气环境下传感器接线方式、空间电磁场对测量回路以及tanδ测量结果的影响,结合电路仿真分析了温、湿度对电流传感器测量角差的影响规律,通过老化试验,研究了元器件老化对信号调理单元等值电气参数和输出相差的影响。理论分析和实验结果验证了多因素对测量二次系统的影响是导致测量结果波动的主要原因。In this paper,combined with engineering practice,the factors affecting the error of online monitoring of the dielectric loss tangent value tanδare analyzed.A complex equivalent circuit model considering multi-component parameters including bushings,current sensors,signal channels and signal conditioning units is established,and the main equivalent electrical parameters in the circuit model are obtained through experiments.A high and low voltage test platform was built to simulate the casing dielectric loss measurement,simulate the sensor wiring method under complex electromagnetic and atmospheric environments,the influence of the space electromagnetic field on the measurement loop and the tanδmeasurement results,and combined with circuit simulation,the influence of temperature and humidity on the angle difference measured by the current sensor is analyzed.Through the aging test,the influence of component aging on the equivalent electrical parameters and output phase difference of the signal conditioning unit is studied.Theoretical analysis and experimental results verify that the influence of multiple factors on the measurement secondary system is the main reason for the fluctuation of the measurement results.
关 键 词:套管 介质损耗角正切值 在线监测 电路模型 误差分析
分 类 号:TM216.5[一般工业技术—材料科学与工程] TM835.4[电气工程—电工理论与新技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.145.79.94