中国与澳大利亚在超高层建筑中消火栓系统设计对比  被引量:1

Comparison of fire hydrant system design between China and Australia in super high-rise buildings

在线阅读下载全文

作  者:王帅 Wang Shuai(WSP&Parsons Brinckerhoff Engineering Technology(Beijing)Co.,Ltd.,Beijing 100102,China)

机构地区:[1]科进柏诚工程技术(北京)有限公司,北京100102

出  处:《给水排水》2020年第8期159-170,共12页Water & Wastewater Engineering

摘  要:基于我国与澳大利亚的消火栓系统规范,以1座建筑高度为299.3 m的超高层建筑项目作为项目案例,分别按两国规范设计出2种消火栓系统方案.对2种方案进行对比,分析两国超高层消火栓系统的各自特点,得到澳大利亚超高层消火栓系统值得借鉴的地方,提出对我国消火栓系统的设计建议.Based on the hydrant system codes of China and Australia,two hydrant system schemes are designed according to the codes of China and Australia,taking a super high-rise building project with a building height of 299.3 m as the project case.By comparing the two schemes and analyzing the respective characteristics of the two countries’super high-rise hydrant systems,the author obtained the Australia’s super high-rise hydrant system which is worthy of our reference,and put forward some suggestions on the design of China's hydrant system.

关 键 词:室内 外消火栓 消防水泵接合器 高位消防水池 系统分区 重力供水 减压阀栓口压力 保护半径 设计流量 

分 类 号:TU822[建筑科学]

 