750 kV联络变压器短时感应耐压试验(ACSD)研究  

Study of Short-duration Induced AC Withstand Test for 750kV Interconnecting Transformer

在线阅读下载全文

作  者:彭朝亮 陈红日 梁红胜 胡志武 PENG Chao-liang;CHEN Hong-ri;LIANG Hong-sheng;HU Zhi-wu(Wuhan NARI Limited Liability Company of State Grid Electric Power Research Institute,Wuhan 430074,China)

机构地区:[1]国网电力科学研究院武汉南瑞有限责任公司,湖北武汉430074

出  处:《通信电源技术》2020年第11期23-25,28,共4页Telecom Power Technology

摘  要:基于750 kV联络变压器对短时感应耐压试验(ACSD)方法进行了研究,针对目前变压器电压等级及容量的增加,电压支撑法的运用有效解决了兼顾考核高电压等级变压器各线端纵绝缘和相间绝缘强度的要求。经过对750 kV联络变压器中线点电压支撑试验线路各线端电压进行准确计算,通过出厂试验验证了该试验方案的可行性。Based on 750 kV Interconnecting Transformer,the essay studied the Short-duration induced AC withstand Test for 750 kV Interconnecting Transformer. For the capacity and voltage levels of transformer increased. Voltage support method effectively solved the assessment of each ends vertical insulation and phase insulation of high voltage level transformer. Based 750 kV transformer voltage support each neutral point voltage test circuit,calculated each line voltage,and the test results verified the way viable.

关 键 词:750 kV联络变压器 短时感应耐压试验(ACSD)试验 电压支撑法 

分 类 号:TM407[电气工程—电器]

 