摘 要:以两侧变电站不同主接线方式下220 kV线路保护改造为例,分析了3/2接线侧断路器失灵保护跳开双母线接线侧断路器时该线路远跳功能的实现方法,并提出了可行的优化措施,为线路改造前的设备选型工作提供指导。所提措施不仅降低了二次设备改造复杂度,还降低了设备投资及后期维护成本。The modification of 220 kV transmission line protection under different main connection modes of substations on both sides is taken as an example to analyze the realization method of remote tripping function of the line when the circuit-breaker failure protection on the 3/2 connection side trips the circuit breakers on the double busbar connection side.Feasible optimization measures are proposed to provide guidance on equipment selection before the modification of transmission lines.The proposed measures reduce not only the complexity of secondary equipment modification,but also investment in equipment and subsequent maintenance costs.