一起因接线错误导致阻抗继电器动作的停机事件  

A Shutdown Event that Caused Impedance Relay Action Due to Wiring Error

在线阅读下载全文

作  者:周项超 褚楚 郝旭媛 ZHOU Xiangchao;CHU Chu;HAO Xuyuan(HaiNan Nuclear Power Co.,Ltd.,Changjiang 572733,China)

机构地区:[1]海南核电有限公司,海南昌江572733

出  处:《电工技术》2020年第18期95-97,101,共4页Electric Engineering

摘  要:结合阻抗继电器的工作原理,采用事件发生前后的机组暂态数据计算、运行状态波形分析、现场检查确认等分析方法,对一起应急柴油发电机误停机的事件进行详细分析,得出停机事件的原因为阻抗继电器的A、C两相电流输入接线反接。通过对接线错误的纠正,保证了柴油发电机组的运行安全。Combining the working principle of impedance relay,and using analysis methods such as calculation of unit transient data before and after the event,waveform analysis of operating status,and on-site inspection confirmation,a detailed analysis of an accident of emergency diesel generator shutdown was made.It was concluded that the cause of the shutdown event was the reverse connection of the A and C phase current input wiring of the impedance relay.By correcting the wiring errors,the safety of the diesel generator set was guaranteed.

关 键 词:阻抗继电器 波形分析 柴油发电机 

分 类 号:TM588.3[电气工程—电器]

 