检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:于游 田景辅 李涛 YU You;TIAN Jingfu;LI Tao(State Grid Liaoning Electric Power Co.,Ltd.,Shenyang 110006,Liaoning,China;Dalian Power Supply Company,State Grid Liaoning Electric Power Co.,Ltd.,Dalian 116000,Liaoning,China)
机构地区:[1]国网辽宁省电力有限公司,辽宁沈阳110006 [2]国网辽宁省电力有限公司大连供电公司,辽宁大连116000
出 处:《电网与清洁能源》2020年第7期64-68,74,共6页Power System and Clean Energy
基 金:国家电网有限公司科技项目(2019YF-21)。
摘 要:在平行双回线内部发生接地故障时,反时限零序电流保护可能会出现误动,靠近故障端的保护速动性较差,故障线路两端的保护动作存在配合程度低,且灵敏度低的问题。为解决平行双回线对反时限零序电流保护的影响,提出改进算法,通过改变时间整定系数,使反时限特性曲线上下移动,从而配合其他曲线实现反时限零序电流的保护,解决平行双回线反时限零序电流保护误动问题。设定延时时间,提高保护选择性动作的正确性,确保快速切除接地故障。通过对比实验验证改进算法的有效性,结果表明,平行双回线出现接地故障时,研究算法可以有效减少反时限零序电流保护误动情况,增强保护速动性,实现故障保护选择性动作的灵敏配合。When the ground fault occurs inside the parallel double-circuit line,the reverse time-limit zero-sequence current protection may misoperate,and the protection near the fault end is poor in quick action and the protection at both ends of the fault line suffers from low coordination and low sensitivity.In order to address the effect of parallel double-circuit on the reverse time zero-sequence current protection,an improved algorithm is proposed in this paper.With this algorithm,the inverse time zero-sequence current protection curve is moved up and down by changing the time setting coefficient,so as to,together with other curves,realize the protection of inverse time zero sequence current and solve the misoperation problem of parallel double circuit inverse time zero sequence current protection.The delay time is set to improve the accuracy of selective protection actions and ensure quick removal of the ground fault.The effectiveness of the improved algorithm is verified by comparing experiments,and the results show that the proposed algorithm can effectively reduce the false motion of the inverse time zero-sequence current protection when the parallel double-circuit fault occurs,enhance the quick action of protection,and realize the sensitive coordination of selective actions for fault protection.
关 键 词:平行双回线 反时限零序电流 零序电流保护 改进算法
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.191.120.131