检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:苑绍迪 刘芳[1] 马力 胡景景 张大鹏[1] Yuan Shaodi;Liu Fang;Ma Li;Hu Jingjing;Zhang Dapeng(Shandong Jianzhu University;Shanghai PanAn Electrical Installation Engineering Co.,Ltd.)
机构地区:[1]山东建筑大学 [2]上海番安机电安装工程有限公司
出 处:《制冷与空调》2020年第9期35-38,共4页Refrigeration and Air-Conditioning
摘 要:建立空气源-水环热泵联合系统的模型,通过改变空气源-水环热泵联合系统的空气源热泵冷凝温度及蒸发温度,得到联合系统不同工况下的最佳性能系数。研究结果表明:在供水温度分别为45℃和50℃时,系统性能系数均在空气源热泵冷凝温度16℃时达到最大值,分别为2.128和1.954,供水温度为55℃时,系统性能系数在空气源热泵冷凝温度18℃时达到最大值1.805;供水温度分别为45℃,50℃和55℃时,单级系统(仅运行空气源热泵系统)、双级系统(空气源-水环热泵联合系统)相互切换的最佳蒸发温度分别为-2℃,-13℃和-23℃。指出根据不同工况及时调整热泵系统的运行方式能够提高系统能效。The model of air-source and water loop heat pump combined system is established.By changing the condensing temperature and evaporating temperature of the airsource heat pump,the optimal COPof the combined system under different operating conditions is obtained.The study results show that when the water supply temperatures are45℃and 50℃,the COPof the system reaches the maximum value at 16℃of the condensing temperature for air-source heat pump,which are 2.128 and1.954,respectively;when the water supply temperature is 55℃,the COPof the system reaches the maximum value at 18℃of the condensing temperature for air-source heat pump,which is 1.805;when the water supply temperatures are 45℃,50℃and 55℃,the optimal evaporating temperatures of the single-stage system(only running the air-source heat pump system)or double-stage system(air-source heat pump and water loop heat pump combined system)are-2℃,-13℃and-23℃,respectively.It is pointed out that by adjusting the operation mode of the heat pump system in time according to different operating conditions,it can improve the energy efficiency ratio of the system.
关 键 词:空气源热泵 水环热泵 性能系数 蒸发温度 冷凝温度
分 类 号:TB6[一般工业技术—制冷工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.3