作 者:李怀强 高露 粟小华 胡勇 盛志文 石东源[3] LI Huaiqiang;GAO Lu;SU Xiaohua;HU Yong;SHENG Zhiwen;SHI Dongyuan(Northwest Power Dispatching and Controlling Center,Xi’an 710048,China;State Grid Xi’an Power Supply Company,Xi’an 710032,China;Huazhong University of Science and Technology,Wuhan 430074,China)
机构地区:[1]国家电网西北电力调控分中心,陕西西安710048 [2]国网西安供电公司,陕西西安710032 [3]华中科技大学,湖北武汉430074
出 处:《电力系统保护与控制》2020年第21期166-172,共7页Power System Protection and Control
基 金:国家自然科学基金项目资助(51777081)。
摘 要:分析了西北电网三起因保护拒动而导致的故障范围扩大事故,指出现有基于最严苛电网运行方式的超高压线路后备保护整定可能导致保护定值灵敏性不足、无法可靠动作的问题。提出了基于非最严苛电网运行方式的超高压线路距离保护整定方法,距离Ⅱ段采用接近于实际的检修方式进行整定,距离Ⅲ段采用考虑对侧故障可靠切除后的运行方式进行整定。该整定方法在改善配合关系的同时,能够最大限度地发挥距离保护对本线和相邻设备的后备作用。实际算例验证了该整定方法的有效性。This paper analyzes three power grid fault range enlargement accidents in the Northwest Power Grid caused by the failure of protection to operate on command. It is pointed out that one of the reasons for this is the insufficient sensitivity of line protection setting because of the existing backup protection coordination method which is based on extreme grid operation modes. A method for coordinating the settings of distance protection for extra-high-voltage lines based on non-extreme grid operation modes is proposed. In this method, zone Ⅱ of the distance protection is coordinated based on modes close to actual maintenance situations, while zone Ⅲ is coordinated using the mode where the opposite-side fault is successfully removed. This method can clarify the coordination relationship of adjacent relays and thus optimize a relay’s backup protection function for the line where it is installed and its downstream equipment. The effectiveness of the proposed method is verified through experiments.
分 类 号:TM726.1[电气工程—电力系统及自动化] TM773
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.233