作 者:宋伟[1] 杨家明[1] 张华北 郭建良 Song Wei;Yang Jiaming;Zhang Huabei;Guo Jianliang(North China University of Technology,Beijing,China;不详)
机构地区:[1]北方工业大学 [2]江苏盛世节能科技有限公司 [3]同能创达科技(北京)有限公司
出 处:《暖通空调》2020年第11期107-112,共6页Heating Ventilating & Air Conditioning
基 金:国家自然科学基金资助项目(编号:41602278);北方工业大学青年拔尖人才培育计划资助项目(编号:XN018032);北方工业大学青年毓杰人才计划资助项目(编号:18XN154-006);北方工业大学科技创新工程资助项目(编号:18XN149)。
摘 要:为解决低负荷下冷水流量过大导致冷水泵能耗较大的问题,将一种新的控制策略应用于流量控制阀。搭建了模拟试验台,对空调冷水系统不同风量和不同供水温度下的阀门开度、冷水流量、供回水温差和冷水泵功率进行了比较,验证了该控制阀的控制特性及节能效果。结果显示:控制阀控制回水温度的效果较好,且当房间负荷小于风机盘管最大供冷量时,控制阀能够有效调节冷水流量,提高供回水温差并降低冷水泵功耗;当供水温度为7℃,风机盘管在低(325m3/h)、中(500m3/h)、高(600m3/h)挡风量下,平均供回水温差分别为4.79、4.39,4.97℃,与使用通断型两通阀相比,平均冷水流量分别降低47.71%、39.07%.31.28%,冷水泵能耗分别降低12.20%,11.31%.10.66%;中挡风量下,供水温度为7、8、9℃时,平均供回水温差分别为4.39、3.56、3.33℃,与使用通断型两通阀相比,平均冷水流量分别降低39.07%,11.35%,18.21%,冷水泵能耗分别降低11.31%,5.09%.7.78%.In order to solve the high energy consumption problem of chilled water pump caused by excessive flow rate of chilled water at low load, proposes a new control strategy for flow control valves. Sets up a simulation test bench, compares the valve opening, chilled water flow rate, temperature difference between supply and return water and chilled water pump power of air conditioning chilled water system at different air rates and water supply temperatures. Verifies the control characteristics and energy saving effect of this control valve. The results show that the valve controls the return water temperature better, and when the room load is less than the maximum cooling capacity of the fan coil unit(FCU), the control valve can effectively adjust the chilled water flow rate, improve the temperature difference between supply and return water, and reduce the power consumption of chilled water pump. When the supply water temperature is 7 ℃, the average temperature difference of supply and return water is 4.79 ℃, 4.39 ℃ and 4.97 ℃ at low(325 m^3/h), medium(500 m^3/h) and high(600 m^3/h) air rates, respectively. Compared with the on-off valve in same conditions, average chilled water flow rate decreases by 47.71%, 39.07% and 31.28%, respectively, and the energy consumption of chilled water pump decreases by 12.20%, 11.31% and 10.66%, respectively. When the air rate is at medium and the temperature of supply water is 7 ℃, 8 ℃ and 9 ℃, the average temperature difference of supply and return water is 4.39 ℃, 3.56 ℃ and 3.33 ℃, respectively. Compared with the on-off valve, the average chilled water flow decreases by 39.07%, 11.35% and 18.21%, respectively, and the energy consumption of chilled water pump decreases by 11.31%, 5.09% and 7.78%, respectively.
关 键 词:冷水系统 流量控制 阀冷水泵能耗 冷水流量 供回水温差 节能
分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.15.145.122