作 者:李伟 方超颖 王森 李志忠 鲁海亮[3] 文习山[3] 李纯[3] LI Wei;FANG Chaoying;WANG Sen;LI Zhizhong;LU Hailiang;WEN Xishan;LI Chun(State Grid Shanxi Electric Power Research Institute,Xi'an 710100,China;State Grid Fujian Electric Power Research Institute,Fuzhou 350007,China;School of Electrical Engineering and Automation,Wuhan University,Wuhan 430072,China)
机构地区:[1]国网陕西省电力公司电力科学研究院,西安710100 [2]国网福建省电力有限公司电力科学研究院,福州350007 [3]武汉大学电气与自动化学院,武汉430072
出 处:《电瓷避雷器》2020年第5期205-210,共6页Insulators and Surge Arresters
基 金:国家电网有限公司总部科技项目“基于现场冲击实验的输电线路雷击暂态特性、模型和接地防护措施研究”(编号:SGTYHT/17-JS-199)。
摘 要:为了准确计算雷击杆塔时塔身的电压响应,针对杆塔的冲击特性已经开展了大量的研究,但这些研究大多针对单独的杆塔,未考虑线路中杆塔的情况。本文基于FDTD方法建立了雷击杆塔的计算模型,并通过设置电压引线和电流引线模拟了测试回路存在的情况。雷击杆塔时杆塔的冲击特性与电流波形密切相关,雷电流下杆塔的冲击特性介于阶跃电流和斜波电流下的冲击特性之间。当只考虑流入杆塔部分的电流和塔顶电位时,带线路杆塔的冲击阻抗取值与单独杆塔的冲击阻抗取值几乎无区别。对杆塔的冲击阻抗进行测量时,测量系统与测量对象之间存在的电磁耦合会对结果造成影响,雷击情况下的冲击阻抗值比测试回路下的冲击阻抗值要大19%-34%。In order to accurately calculate the voltage response of the tower when lightning strikes,a lot of research has been carried out on the surge characteristics of the tower,but most of these studies are about individual tower,without considering the tower with overhead lines. In this paper,the calculation model of lightning strikes to the tower is established based on FDTD method,and the existence of measurement circuit is simulated by setting voltage lead and current lead. The lightning striking characteristics of the tower is closely related to the current waveform,and the surge characteristics of the tower under lightning current are between the surge characteristic under the step current and the ramp current. When only the current flowing into the tower and the tower top potential are considered,the value of the surge impedance of the tower with overhead lines is almost indistinguishable from the value of the surge impedance of the individual tower. When measuring the surge impedance of the tower,the electromagnetic coupling between the measuring system and the measuring object will affect the result. The surge impedance value under lightning strike is 19% ~ 34% larger than that under the measurement circuit.
分 类 号:TM75[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.17.9.170