摘  要:介绍了二次重合闸的原理和整定方法,分析了一起近端故障保护二次重合闸拒动的事件,发现事件原因是弹簧储能时间与保护控制回路断线告警时间不匹配,引起重合闸瞬时放电。最后给出了解决方案,并通过试验验证了解决方案的有效性。The principle and setting method of secondary reclosing were introduced.An incident of near-end fault protection secondary reclosing failure was analyzed.It was found that the cause of the event was that the spring energy storage time did not match with the protection control circuit disconnection alarm time,which caused the reclosing instantaneous discharge.Finally,the solution was given,and the effectiveness of the solution was verified through experiments.

关 键 词:二次重合闸 储能时间 控制回路 断线 