抽水蓄能机组甩负荷试验时尾水锥管压力  被引量:6

Draft cone tube pressure of pumped-storage power unit in load rejection test

在线阅读下载全文

作  者:张飞 王宪平 Zhang Fei;Wang Xianping(Technology Center of State Grid Xinyuan Company Ltd.,Beijing 100053,China;Voith Hydro Power Generation Shanghai Ltd.,Shanghai 200240,China)

机构地区:[1]国网新源控股有限公司技术中心,北京100053 [2]上海福伊特水电设备有限公司,上海200240

出  处:《农业工程学报》2020年第20期93-101,共9页Transactions of the Chinese Society of Agricultural Engineering

基  金:国家电网公司科技项目(52573020000B);国家自然科学基金资助项目(51809082);中国水科院基本科研业务费项目(HM0145B242020)。

摘  要:抽水蓄能机组水力调节过渡过程计算控制核心要求之一是尾水锥管压力不超过设计值。设计值是根据水力过渡过程理论的一维数值模拟“计算值”加上一定“压力脉动修正”量和“计算误差”后计算获得。长期以来,尾水锥管压力计算值与尾水锥管压力测量值之间仍存在一定偏差,导致采用实测数据对计算结果进行评判时不能得到合理的解释与评价。为解决调节保证计算与试验验证之间的分歧,该研究对调节保证计算时尾水锥管压力最小值含义进行了阐释,梳理了调节保证计算与试验中涉及尾水锥管压力的相关国内标准。在此基础上,以洪屏抽水蓄能电站调试阶段四台机组甩额定负荷时的实测尾水锥管压力为研究对象,首先分析了压力测点的测量条件,采用短时傅里叶变换进行频率特性分析,验证了测试数据的有效性;其次采用Savitzky-Golay滤波器分离出了表征一维数值模拟断面平均压力计算值的压力趋势与表征流动复杂性的压力脉动,针对压力脉动项研究了峰峰值与时长的关系并获得了压力脉动项最大峰峰值,验证了趋势项与一维数值模拟之间的一致性;随后采用压力脉动项最大峰峰值对数值模拟和实测压力趋势项极值进行修正;最后总结形成了尾水锥管压力调节保证设计值的修正流程。案例研究表明:采用截止频率为0.1~0.2倍转频的低通滤波器可以有效分离出与一维数值模拟一致的尾水锥管压力趋势项;采用3~4个旋转周期数对应的压力脉动数据进行分析可以获得压力脉动项的最大峰峰值;利用压力脉动最大峰峰值对一维数值模拟极值进行修正能够实现调节保证的有效设计与验证。该研究为抽水蓄能机组调节保证设计与验证提供了有效支撑。One of the key control parameters in hydraulic transient process of pumped-storage power unit is draft cone tube pressure,which should be within the design value.The design value is calculated by one dimension mathematical model of hydraulic transient theory with considering on certain pressure pulsation correction and calculation error.For a long time,there is non-negligible deviation between the calculated value by one dimension numerical simulation and the measured value of draft cone tube from on-site load rejection test.Henceforth,once engineers use measured values to check calculation results,they can not get reasonable explanation and evaluation between simulation results and measured values.In order to settle the difference between regulation guarantee calculation value and measured value,minimum pressure of draft cone tube was clarified from multiple perspectives in this paper,and Chinese standards or codes relating to hydraulic transient calculation were reviewed.The standard research indicates that for pumped storage unit,the minimum draft cone tube pressure should not below-0.08MPa in any circumstances.Measured draft cone tube pressure data of the rated load rejection tests performed in Hongping pumped storage power station during commissioning period was investigated.Firstly,field measuring conditions of draft cone tube pressure was thoroughly assessed and confirmed,and the validity of measured pressure was verified by using short-time-Fourier-transform to analyse the frequency characteristics.The frequencies of four draft cone tube pressure are similar,of which are low frequency component and rotor-stator frequency.The main frequencies are lower than first order eigen frequency of measuring pipes.The obtained data can be regarded as near wall measured pressure.Secondly,Savitzky-Golay filter was employed to separate trend and pulsation of measured draft cone tube pressure.The separated pressure trend can be deemed as the average section pressure of draft cone tube in one dimension numerical simulatio

关 键 词:压力脉动 数值模拟 调节保证计算 尾水锥管压力 Savitzky-Golay滤波器 

分 类 号:TK734[交通运输工程—轮机工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象