检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:郝秋林 张亮 HAO Qiu-lin;ZHANG Liang(China Mobile Guangdong Guangzhou Branch,Guangzhou 510000,China)
机构地区:[1]中国移动广东广州分公司,广东广州510000
出 处:《通信电源技术》2020年第S01期373-377,共5页Telecom Power Technology
摘 要:针对广州移动某通信机楼运行过程存在的问题,从中央空调系统控制和能源监管两个方面,提出了融合多种空调节能技术和能源管理方法的综合节能改造方案。改造结果表明,空调系统节能率可达31.35%,PUE值可提高8.64%,年节电费用达147.25万元,具有良好的经济效益。Considering central air-conditioning system control and energy supervision,this paper put forward a comprehensive energy-saving reconstruction program,which integrates multiple air-condition energy-saving technologies and energy management methods,aiming at the problems during the operation of communication building in Guangzhou.The results show that central air-conditioning system energy saving rate is 31.35%,and PUE is improved by 8.64%.The program proposed reduces 147.25 million yuan power consumption in a year,and good economic benefit has already been gained.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.63