检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:黄磊 HUANG Lei(Changzan Shimen Power Generation Co.,Ltd.,Changde 415300,China)
出 处:《湖南电力》2020年第6期73-76,共4页Hunan Electric Power
摘 要:火电机组发变组绝缘是机组冷备用转热备用时重要的一项电气绝缘性能指标。在日常运行维护过程中,机组停运时发变组绝缘并不能长期自我保持合格。对发变组绝缘低产生的薄弱环节展开逐项治理,增加吹扫管路将主变、高厂变20 kV侧升高座纳入到离相封母系统内,主动打破、重构其密封结构,将离相封母系统改造为半开放式系统,引导离相封母空气向外、定向流通,使发变组绝缘长时间冷态下可保持在100 MΩ以上。相较DMC等绝缘材料升级,其投资少、易实现,且系统免维护。The insulation of generator-transformer unit in thermal power unit is an important electrical insulation performance index when the cold standby unit is switched to the hot standby unit. In the daily operation and maintenance process, the insulation of generator-transformer unit can not keep up with itself for a long time when the unit is shut down. The weak links caused by the low insulation of the generator-transformer unit are dealt with one by one, and the 20 kV side risers of the main transformer and the high power plant transformer are brought into the isolated phase sealing bus system by adding the blowing pipe, and the sealing structure is broken down and reconstructed on the initiative. The separated phase sealing bus system is reformed into a semi-open system, which leads the separated phase sealing bus air to flow outwards and directionally, so that the insulation of generator-transformer group can be kept above 100 MΩ for a long time. Compared with DMC and other insulation material upgrade, it is less investment, easy to realize with free maintenance.
关 键 词:发变组绝缘 防污闪涂料 微正压系统 变压器升高座 吹扫管路 半开放式离相封闭母线
分 类 号:TM855[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.144.255.53