一种极柱接线端的连接方式及对温升的影响  被引量:1

A connection method of pole terminal and its influence on temperature rise

在线阅读下载全文

作  者:李婷婷[1] 武岳[1] 李志刚[1] 刘继颖[1] 孔国威 LI Tingting;WU Yue;LI Zhigang;LIU Jiying;KONG Guowei(Offshore Oil Engineering Co.,Ltd.,Tianjin 300452,China;Beijing Shuangjie Electric Co.,Ltd.,Beijing 100089,China)

机构地区:[1]海洋石油工程股份有限公司,天津300452 [2]北京双杰电气股份有限公司,北京100089

出  处:《电气应用》2021年第3期79-82,共4页Electrotechnical Application

摘  要:当前在电网改造升级的推动下,海上油气田对更大容量、更高额定电流的中压开关设备产品需求不断提高。但目前常规中压断路器固封极柱因紧固连接失效常常导致产品无法可靠运行,无法满足大电流产品的热稳定要求。为此,选用一种新型的复合紧固连接形式,并对此进行了数值分析和试验研究。结果表明这种复合紧固连接具有比常规连接更优异的温升特性表现。At present,driven by the transformation and upgrading of power grids,offshore oil and gas fields have continuously increasing demand for medium voltage switchgear products with larger capacity and higher rated current.However,at present,the solid-sealed poles of conventional medium voltage circuit breakers often fail to operate reliably due to the failure of the fastening connection,and cannot meet the thermal stability requirements of high-current products.For this reason,a new type of composite fastening connection is introduced,and numerical analysis and experimental research on it are conducted.The results show that this composite fastening connection has a very superior temperature rise performance than conventional connections.

关 键 词:固封极柱 热稳定要求 复合连接 温升 

分 类 号:TM561[电气工程—电器]

 