作 者:聂立 蔡润夏 鲁佳易 程伟 张文杰 巩李明 薛大勇 张缦[3] 杨海瑞[3] 吕俊复[3] NIE Li;CAI Run-xia;LU Jia-yi;CHENG Wei;ZHANG Wen-jie;GONG Li-ming;XUE Da-yong;ZHANG Man;YANG Hai-rui;LV Jun-fu(College of Energy Engineering,Zhejiang University,Hangzhou 310027,China;Clean Combustion and Flue Gas Purification Key Laboratory of Sichuan Province,Chengdu 611731,China;Key Laboratory for Thermal Science and Power Engineering of Ministry of Education,Tsinghua University,Beijing 100084,China)
机构地区:[1]浙江大学能源工程学院,浙江杭州310027 [2]清洁燃烧与烟气净化四川省重点实验室,四川成都611731 [3]清华大学热科学与动力工程教育部重点实验室,北京100084
出 处:《浙江大学学报(工学版)》2021年第3期578-585,共8页Journal of Zhejiang University:Engineering Science
基 金:国家重点研发计划资助项目(2016YFB0600204).
摘 要:为了解决660 MW超超临界循环流化床锅炉外置换热器中受热面的壁温偏差问题,通过数值计算,复现600 MW超临界循环流化床锅炉外置换热器壁温分布,并将该方法应用到相同尺寸的超超临界循环流化床锅炉外置换热器壁温计算中.通过对边壁区域3片管屏工质节流,从工质侧解决超超临界循环流化床锅炉外置换热器壁温偏差问题,使受热面计算壁温偏差控制在30℃以内,实现受热面管材安全运行.通过冷态试验,发现颗粒侧传热系数沿外置换热器宽度方向呈现马鞍形的双峰分布,传热系数最大值出现在距离边壁约0.2倍宽度范围内,通过调整边壁区域气体速度可以提高该区域的传热系数,为运行过程减缓局部偏差提供参考.A wall temperature distribution of the external heat exchanger of 600 MW supercritical circulating fluidized bed boiler was reproduced by numerical calculation, in order to solve the wall temperature deviation of the external heat exchanger of 660 MW ultra supercritical circulating fluidized bed boiler. The result was applied to the calculation of wall temperature of the same size external heat exchanger of ultra-supercritical circulating fluidized bed boiler. By throttling the working medium of three tube platens near side wall, the calculated wall temperature deviation of external heat exchanger of ultra-supercritical circulating fluidized bed boiler was solved. The wall temperature deviation of heating surface could be controlled within 30℃ to keep safe operation of heating surface tubes. Experimental results show that the heat transfer coefficient of the particle side presents a saddle shaped bimodal distribution along the width direction of the external heat exchanger, and the maximum value of the heat transfer coefficient appear at about 0.2 times width near the side wall. By adjusting the gas velocity in the side wall area, the heat transfer coefficient can be improved, so as to provide guidance for slowing down the local deviation in the operation process.
关 键 词:超超临界 循环流化床 锅炉 外置换热器 壁温偏差
分 类 号:TK229.6[动力工程及工程热物理—动力机械及工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.3