严陵工业园综合污水处理厂工程设计  被引量:4

Engineering design of comprehensive wastewater treatment plant in Yanling Industrial Park

在线阅读下载全文

作  者:谭周权 TAN Zhouquan(Lanzhou Urban Construction Design Institute,Lanzhou 730050,China)

机构地区:[1]兰州市城市建设设计院,兰州730050

出  处:《给水排水》2021年第5期90-95,共6页Water & Wastewater Engineering

摘  要:严陵工业园综合污水生化性较差、有机物难以降解、COD、含氮污染物浓度较高。根据园区水质特点和排放要求,该工业园污水处理厂通过预处理-水解酸化-改良型AAO-高效沉淀-臭氧接触氧化-曝气生物滤池组合工艺处理本园区综合污水,并采用超滤-反渗透工艺对处理后的部分废水继续净化再作为园区企业再生水进行回用。当工业园污水平均处理量为2810m^(3)/d时,经过处理后的水质符合排放要求,经过回用工艺处理的水质满足《工业循环冷却水处理设计规范》(GB50050-2007)规定的再生水水质标准及相应企业回用要求,平均单位经营成本为4.02元/m^(3)。Yanling Industrial Park comprehensive wastewater had poor biochemical property,difficult degradation of organic matter and high concentration of COD and nitrogen pollutants.According to the water quality characteristics and discharge requirements of the park,comprehensive sewage in the park was treated by combined process of"pretreatment/hycrolytic acidification/modified AAO/high efficiency sedimentation/ozone contact oxidation/biological aerated filter"in the industrial park sewage treatment plant.And the ultrafiltration reverse osmosis process was used to purify the part of treated wastewater and reuse it as reclaimed water for enterprises in the park.When the average wastewater treatment capacity of the industrial park was 2810 m^(3)/d,the effluent quality of the project fully meets the discharge standard,and the water quality treated by the reuse process met the reclaimed Water quality standard specified in the code for design of industrial circulating cooling water treatment(GB 50050-2007)and the reuse requirements of corresponding enterprises.The average unit operating cost of this project was 4.02 yuan/m^(3).

关 键 词:改良型AAO 臭氧接触氧化 曝气生物滤池 超滤-反渗透 回用 单位经营成本 

分 类 号:TU992[建筑科学—市政工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象