Transmission Line Distance Protection Under Current Transformer Saturation  被引量:1

在线阅读下载全文

作  者:Yuping Zheng Tonghua Wu Feng Hong Gang Yao Jimin Chai Zhinong Wei 

机构地区:[1]the College of Energy and Electrical Engineering,Hohai University,Nanjing 210098,China [2]State Key Laboratory of Smart Grid Protection and Control,NARI Group Corporation,Nanjing 211106,China [3]Changzhou Institute of Technology,Changzhou 213032,China

出  处:《Journal of Modern Power Systems and Clean Energy》2021年第1期68-76,共9页现代电力系统与清洁能源学报(英文)

基  金:supported by Science and Technology Program of State Grid Corporation of China “Research on Fault Coupling Characteristics and New Protection Principle of AC/DC Hybrid Power Grid”。

摘  要:Conventional transmission line distance protection approaches are subject to malfunction under reverse fault-induced current transformer(CT) saturation for the typically employed breaker-and-a-half configuration. This paper addresses this issue by proposing a new distance protection approach that combines the blocking and unblocking criteria of distance protection based on the values of incomplete differential current,operation voltage, and current harmonic content. The proposed approach is verified by theoretical analysis, dynamic simulation testing, and field operation to ensure that the obtained distance protection is reliable and refrains from operating unnecessarily under reverse fault-induced CT saturation in the breaker-and-ahalf configuration. Meanwhile, the proposed approach is demonstrated can operate reliably when forward faults occur or various reverse faults are converted to forward faults.

关 键 词:Breaker-and-a-half configuration current transformer(CT)saturation distance protection power frequency variation operation voltage 

分 类 号:TM773[电气工程—电力系统及自动化] TM452

 