摘 要:通过对国内已建设投运的1000 MW机组高位收水冷却塔的设计计算数据和测试值进行对比分析和总结,对搁置式布置的淋水填料的阻风面积取值进行研究,对设计计算方法进行优化和改进,为高位收水冷却塔的自主化设计提供参考。The comparison analysis and summary of the design calculation data and the test value of cooling tower with WCD in a running 1000 MW power unit were carried out.This paper studies the value of the wind resistance area of the shelved water drenching packings,and optimizes and improves the design method,providing a reference for the indigenous design of the cooling tower with WCD.
关 键 词:高位收水冷却塔 阻力性能 热力性能 出塔水温 淋水填料阻风面积 梁柱阻风面积折减系数