作 者:黄维[1] 郭海涛 王林[1] 曹晓斌[3] 杜浩 HUANG Wei;GUO Haitao;WANG Lin;CAO Xiaobin;DU Hao(Electrification Design and Research Institute,China Railway Siyuan Survey and Design Group Co.,Ltd.,Wuhan 430063,China;China Railway Guangzhou Group Co.,Ltd.,Guangzhou 510088,China;School of Electrical Engineering,Southwest Jiaotong University,Chengdu 610031,China)
机构地区:[1]中铁第四勘察设计院集团有限公司电气化设计研究院,武汉430063 [2]中国铁路广州局集团有限公司供电部,广州510088 [3]西南交通大学电气工程学院,成都610031
出 处:《铁道标准设计》2021年第7期183-187,共5页Railway Standard Design
基 金:中铁第四勘察设计院集团有限公司科技研究计划课题(2019K052)。
摘 要:接触网供电线的上网隔离开关发生接地短路常造成牵引变电所及分区亭二次系统故障,通过试验研究接触网支柱接地回流状态对支柱上的二次保护设备的影响。制定接触网上网隔离开关短路试验方案,试验得到接触网支柱接地回流通畅与不畅两种状态下短路对支柱二次系统的影响,测得牵引变电所二次系统各点的电压以及通过不同路径的回流电流。通过对试验结果进行分析,发现当回流路径通畅时,支柱接地极电压升差仅为35 V,不会造成二次系统损坏;回流路径断开时,短路电流在支柱基础上产生高压,暂态电压峰值达到6400 V,导致将二次设备击穿。研究发现,加热管、三孔插座和SPD是二次保护设备绝缘薄弱环节,击穿电压在2200 V左右,SPD在该情况下不能起到保护作用。The grounding short circuit of the disconnector of catenary power supply line often causes the secondary system fault of traction substation and partition kiosk.Therefore,this paper studies the influence of the grounding return state of OCS pillar on the secondary protection equipment through experiments.The short-circuit test scheme of OCS on-line disconnector is formulated.The influences of short-circuit on the secondary system of OCS under two states of unobstructed and blocked grounding return current are obtained.The voltage at each point of the secondary system of traction substation and the return current through different paths are measured.The analysis of test results finds that when the return path is smooth,the voltage rise difference of the pillar grounding electrode is only about 35 V,which will not cause damage to the secondary system;when the return path is disconnected,the short-circuit current will generate high voltage on the foundation of the pillar,and the peak value of the transient voltage will reach up to 6400 V,which will lead to the breakdown of the secondary equipment.It is found that the heating pipe,three hole socket and SPD are the weak points of the secondary protection equipment insulation,the breakdown voltage is about 2200 V,and SPD fails to play a protective role in this case.
关 键 词:牵引变电所 短路过电压 隔离开关 二次系统 直供方式 接触网 电气化铁道
分 类 号:U224[交通运输工程—道路与铁道工程] U223.8
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.124