作 者:王砚平 鲍威[1] 李赢 姚斯磊 郭瑞鹏[1] 林玲 况静 WANG Yanping;BAO Wei;LI Ying;YAO Silei;GUO Ruipeng;LIN Ling;KUANG Jing(College of Electrical Engineering,Zhejiang University,Hangzhou 310027,China;Zhoushan Power Supply Company of State Grid Zhejiang Electric Power Co.,Ltd.,Zhoushan 316000,China)
机构地区:[1]浙江大学电气工程学院,浙江杭州310027 [2]国网浙江省电力有限公司舟山供电公司,浙江舟山316000
出 处:《电力自动化设备》2021年第7期167-175,共9页Electric Power Automation Equipment
基 金:国家自然科学基金资助项目(51777184)。
摘 要:考虑N-1故障的安全约束机组组合问题规模庞大,对其进行数值求解十分困难。为此,基于直流潮流和线路开断分布因子,建立混合整数线性规划模型并提出约束削减方法。约束削减方法包括两步:根据并联支路潮流之间的关系选出需要监视的支路,以减少并联支路的安全约束;推导故障态潮流的上界,将其与故障态支路容量进行比较,以消除冗余的故障态安全约束。该约束削减方法可以在不改变最优解的前提下,大幅缩减安全约束机组组合问题的规模以及求解时间。IEEE 30和IEEE 118节点测试系统的仿真分析结果验证了所提模型及约束削减方法的有效性。The scale of SCUC(Security-Constrained Unit Commitment)problem considering N-1 contingency is huge,and its numerical solution is very difficult,for which,a mixed-integer linear programming model is built and a constraint-reduction method is proposed.The constraint-reduction method includes two steps:the branches needed to be monitored are selected according to the relationship of power flow between parallel branches,so that the security constraints of parallel branches are reduced;the upper bound of post-contingency power flow is deduced and compared with the branch capacity of post-contingency to remove redundant post-contingency security constraints.The constraint-reduction method can greatly reduce the scale and solution time of SCUC problem without changing the optimal solution.The simulative and analysis results of IEEE 30-and 118-bus test systems verify the effectiveness of the proposed model and constraint-reduction method.
关 键 词:安全约束机组组合 N-1故障 混合整数线性规划 约束削减方法 监视支路 故障态潮流上界
分 类 号:TM73[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.145