一起干式互感器的局部放电缺陷分析  被引量:1

Partial discharge defect analysis of a dry-type mutual inductor

在线阅读下载全文

作  者:梁军龙 徐肖伟 Liang Junlong;Xu Xiaowei(Yunnan Electric Power Research Institute,Yunnan Power Grid Co.,Ltd,Kunming,650217,China)

机构地区:[1]云南电网有限责任公司电力科学研究院,昆明650217

出  处:《云南电力技术》2021年第3期46-49,共4页Yunnan Electric Power

摘  要:本文分析了一起典型的因为生产制造缺陷造成的干式互感器局部放电现象,阐述了脉冲电流法的局部放电检测和紫外成像技术原理。对缺陷进行原因分析,对同类型的干式互感器进行对比试验,然后得出缺陷的原因,最后通过在Comsol Multiphysics软件中进行二维建模,对分析的结果进行验证,并给出处理和防范的建议。This paper analyzes a typical partial discharge phenomenon of dry transformers caused by manufacturing defects,and expounds the principles of local discharge detection and ultraviolet imaging technology of pulse current method.The cause analysis of defects,the comparison test of the same type of dry transformer,and then the cause of the defects,and finally through the two-dimensional modeling in The Multiphysics software,the results of the analysis are verified,and recommendations for treatment and prevention are given.

关 键 词:干式互感器 局部放电 紫外成像检测 

分 类 号:TM74[电气工程—电力系统及自动化]

 