500 kV主变压器总烃含量异常增高分析及处理  被引量:1

Analysis and Treatment of Abnormal Increase of Total Hydrocarbon Content in a 500 kV Main Transformer

在线阅读下载全文

作  者:姜德政[1] 熊舟 叶华松[1] 任波[1] 周平[1] JIANG Dezheng;XIONG Zhou;YE Huasong;REN Bo;ZHOU Ping(Three Gorges Hydropower Plant, China Yangtze Power Co., Ltd., Yichang 443133, China)

机构地区:[1]中国长江电力股份有限公司三峡水力发电厂,湖北宜昌443133

出  处:《水电与新能源》2021年第7期14-16,共3页Hydropower and New Energy

摘  要:利用变压器油中溶解特征气体的组分及含量可识别变压器潜伏性的故障。基于某大型变压器总烃含量增高的原因分析和处理过程,通过产气速率计算、三比值法,结合电气试验,潜油泵检查等方法准确判断变压器故障类型,故障最终得到有效处理。The composition and content of dissolved characteristic gases in transformer oil can be used to identify latent faults of the transformer.The abnormal increase of the total hydrocarbon content in a large-scale transformer is analyzed.Based on the gas production rate values,the three ratio method,electrical tests and submersible pump inspection,the type and possible reasons of the fault are determined.After treatment,the fault is successfully resolved.

关 键 词:变压器 总烃增高 原因分析 处理方法 

分 类 号:TM41[电气工程—电器]

 