作 者:Dehui CHEN Yi XIA Wei LIU Salvatore MANTUANO
机构地区:[1]NARI Technology Co.,LTD,Nanjing 210003,China [2]State Grid Brazil Holding S.A.,Rio de Janeiro 20071-004,Brazil
出 处:《Journal of Modern Power Systems and Clean Energy》2014年第1期87-91,共5页现代电力系统与清洁能源学报(英文)
摘 要:A mal-operation case of busbar protection caused by a dead-zone protection abnormality in the Brazilian Midwest Grid on September 19th,2012,is briefly described.The operation process of pilot distance,automatic re-closure,busbar differential and dead-zone protection,and the emphasis on the logic scheme of dead-zone protection are analyzed.The time delay between the breaker’s main pole and auxiliary contact during re-closure was the main cause in this case,and a defect in the logic allowed it to occur.The differences in dead-zone protection logic between Brazil and China are discussed.A test platform was constructed in the laboratory,and a site simulated experiment was also performed.Possible causes are suggested and test activities are carried out to verify them.Results show the values of practical engineering approaches to the solution.Experience also contributed to avoiding future mal-operations and strengthening the reliability of the protection system,and thus of the power supply in Brazil.
关 键 词:Brazilian power system Power system Relay protection device Dead-zone protection