Islanding detection based on asymmetric tripping of feeder circuit breaker in ungrounded power distribution system  被引量:5

在线阅读下载全文

作  者:Yuwei SHANG Shenxing SHI Xinzhou DONG 

机构地区:[1]State Key Laboratory of Power Systems,Department of Electrical Engineering,Tsinghua University,Beijing 100084,China

出  处:《Journal of Modern Power Systems and Clean Energy》2015年第4期526-532,共7页现代电力系统与清洁能源学报(英文)

摘  要:An islanding detection method in ungrounded power distribution system based on single-phase operating mechanisms of the circuit breaker(CB)is proposed in this paper.When CB opens three phase circuits to form an island,one phase circuit is opened firstly and the other two phase circuits are opened secondly after certain duration.During the period when only one phase circuit is opened,negative sequence voltage with certain duration is obtained at DG side because of the asymmetric operation of the system.After all three phase circuits are opened,the voltage variation direction of the two phases that are secondly disconnected from the grid follows the voltage variation direction of the firstly disconnected phase.Based on the above voltage characteristics,an islanding detection scheme is proposed to identify genuine islanding from system disturbances.The performance of the proposed scheme is tested in PSCAD/EMTDC using a 10 kV distribution network with synchronous DG interconnection.Simulation results demonstrate the proposed method is effective and reliable to detect islanding formation.

关 键 词:Distributed generation Islanding detection Circuit breaker Single-phase operating mechanisms 

分 类 号:TP3[自动化与计算机技术—计算机科学与技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象