作 者:李选平 刘莲 王玉 陈永烨 郑文科 姜益强 Li Xuanping Li;Liu Lianu;Wang Yu;Chen Yongye;Zheng Wenke;Jiang Yiqiang(School of Architecture,Harbin Institute of Technology,Harbin He Longjiang;Key Laboratory of Cold Region Urban and Rural Human Environment Science and Technology,Ministry of Industry and Information Technology,Harbin He Longjiang;China Southwest Architectural Design and Research Institute Corp.Ltd,Chengdu SiChuan)
机构地区:[1]哈尔滨工业大学建筑学院,黑龙江哈尔滨150001 [2]寒地城乡人居环境科学与技术工业和信息化部重点实验室,黑龙江哈尔滨150001 [3]中国建筑西南设计研究院,四川成都610041
出 处:《东北电力大学学报》2021年第2期28-37,共10页Journal of Northeast Electric Power University
基 金:十三五国家重点研发计划课题(2017YFC0702604)。
摘 要:随着经济的发展,对能源的需求日益增加,而间歇供暖能有效地减少能耗,因此对间歇供暖的研究显得格外重要.文中主要研究了间歇供暖在近零能耗建筑内的应用,通过数值仿真方法探索了地板辐射采暖房间在过量/欠量供暖条件下,供热量、保温形式和墙体数量对房间温度、供暖效率及房间能耗的影响.研究分析了各种工况下房间升降温曲线及供暖运行时长,以及各工况下房间供暖效率及能耗程度.结果表明:从3倍供热量到10倍供热量,外保温一面外墙房间的供暖时间比例减小了91.4%,平均能耗减小了64.5%;从3倍供热量到8倍供热量,内保温一面外墙房间与外保温一面外墙房间相比,房间供暖时间比例分别减小了10.9%、2.4%、1.7%、2.0%、1.5%;从3倍供热量到5倍供热量,内保温两面外墙房间的平均能耗要比外保温两面外墙房间分别增加了54.1%、50.3%、32.3%.With the development of economy,the demand for energy is increasing,and intermittent heating can efficiently reduce energy consumption.Therefore,the research on intermittent heating is particularly important.This paper focuses on the application of intermittent heating in near-zero energy building,the effects of heating capacity,insulation form and exterior wall quantity on the temperature change,heating efficiency and energy consumption are investigated in floor radiant heating room with over/under heating system.Numerical simulation is established the research and the temperature rise and fall curves and heating operation time under various working conditions are obtained,and the heating efficiency and energy consumption of the room under various working conditions are analyzed.The results show that when the heating capacity increased from 3 times to 10 times,the ratio of heating time decreases by 91.4%and the average energy consumption decreases by 64.5%in one-exterior wall room with external insulation.When the heating capacity increased from 3 times to 8 times,the ratio of heating time of one-exterior wall room with external insulation decreases by 10.9%,2.4%,1.7%,2.0%and 1.5%separately based on that of one-exterior wall room with inner insulation.When the heating capacity increased from 3 times to 5 times,the ratio of heating time of two-exterior wall room with external insulation decreases by 54.1%,50.3%and 32.3%separately based on that of two-exterior wall room with inner insulation.
关 键 词:地板辐射采暖 过量/欠量供暖 温度变化 能耗分析
分 类 号:TK115[动力工程及工程热物理—热能工程] TU111[建筑科学—建筑理论]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.48