平板过冷却器内结冰行为的实验研究  被引量:1

Experimental Study on Freezing Behavior in Flat-plate Supercooler

在线阅读下载全文

作  者:王锦辉 郑闽锋 李月玲 刘曦 李学来[1] Wang Jinhui;Zheng Minfeng;Li Yueling;Liu Xi;Li Xuelai(College of Chemical Engineering,Fuzhou University,Fuzhou,350116,China;College of Ecological Environment and Urban Construction,Fujian University of Technology,Fuzhou,350118,China;Research Institute of Photocatalysis,Fuzhou University,Fuzhou,350116,China)

机构地区:[1]福州大学石油化工学院,福州350116 [2]福建工程学院生态环境与城市建设学院,福州350118 [3]福州大学光催化研究所,福州350116

出  处:《制冷学报》2021年第4期142-148,157,共8页Journal of Refrigeration

基  金:福建省自然科学基金(2020J01518);福州大学国家环境光催化工程技术研究中心开放课题(NERCEP-201903)项目资助

摘  要:本文设计并搭建了一套过冷水动态制冰系统,开发了一种可视化平板过冷却器,通过实验研究流动和换热对过冷却器内结冰行为的影响,并基于经典成核理论与边界层理论对其作用机理进行解释。实验结果表明:平板过冷却器内存在两种典型结冰行为,结冰行为一表现为过冷却器内不结冰,系统可连续制取冰浆;结冰行为二表现为过冷却器内发生结冰,系统不能制取冰浆。载冷剂进口温度过低、制冰溶液流量过大或过小均会促进结冰行为二的出现,不利于系统制冰稳定性。发生结冰行为二时,相对距离d为0.15的壁面优先发生结冰,且该处壁面的温度总低于其余区域,因此优先发生结冰的局部条件是具有更低的壁面温度。In this study,a dynamic ice-making system with supercooling water was designed and built,and a visual flat-plate supercooler was developed.The influence of flow and heat transfer on the freezing behavior in the flat-plate supercooler was studied by a large number of experiments,and the mechanism was explained by the classical nucleation theory and boundary layer theory.The results shows that there were two types of freezing behavior in the flat-plate supercooler:freezing behavior 1 shows that no freezing occurs in the supercooler and the system can continuously produce ice slurry,and freezing behavior 2 shows that freezing occurs in the supercooler and the system cannot produce ice slurry.The low inlet temperature of the secondary refrigerant and too large or too small flow of ice-making solutions were largely responsible for promoting the occurrence of freezing behavior 2,which was not conducive to the ice-making stability of the system.When freezing behavior 2 occurs,freezing occurs first on the wall with a relative distance d=0.15,where the temperature is always lower than that of the wall with a relative distance d=0.25,0.35,0.45,so the local condition for freezing to occur first is a lower wall temperature.

关 键 词:冰浆 流动与换热 板式换热器 结冰行为 

分 类 号:TB61.1[一般工业技术—制冷工程] TB657.1

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象